Schneider Electric C16H34V160 — Residual Current Breakers (RCCB/RCBO)

Schneider C16H34V160 ComPacT NSX160H MCCB, 160 A, 70 kA

MPNC16H34V160
Active

Schneider Electric ComPacT NSX series, C16H34V160 NSX160H earth leakage circuit breaker, 3P, 160 A, MicroLogic 4.2 electronic trip unit, 70 kA at 415 V AC.

$1,125.64 – $2,569.32Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H34V160 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16H34V160 — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (operating cycles)40000 cycles
C16H34V160 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX160H
C16H34V160 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C16H34V160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C16H34V160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C16H34V160: The H breaking capacity code delivers 70 kA Icu at 380/415 V AC, 65 kA at 440 V, and 100 kA at 220/240 V, all per IEC 60947-2. At 480 V AC the breaker is also rated 65 kA Icu per UL 60947-4-1. This level of interrupting capacity allows the NSX160H to be used as a main or feeder breaker in high-fault installations where downstream coordination with lower-rated devices is required. The 160 A frame size with H rating is a common choice for distribution panels feeding motor control centers or large branch circuits.

Trip unit and protection logic

The MicroLogic 4.2 electronic trip unit is field-adjustable for long-time pickup and delay, short-time fixed delay, and instantaneous pickup. Earth-leakage protection is integrated, with sensitivity set via the IΔn rotary switch. Local signaling uses a flashing green LED for ready-to-operate status, a red LED at 105 % Ir for overload, and an orange LED at 90 % Ir for pre-alarm.

Mounting and environmental ratings

The IP40 enclosure (IK07 impact resistance) suits indoor panel installation in dry environments. Operating altitude is 0–2000 m without derating, with derating required above 2000 m.

Frequently asked questions

What is the breaking capacity of C16H34V160 at 415 V AC?

The breaking capacity is 70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What protection functions does the MicroLogic 4.2 trip unit provide?

The MicroLogic 4.2 provides overload protection (long-time L), short-time short-circuit protection with fixed delay (So), instantaneous short-circuit protection (I), and earth-leakage protection (R).

Where can I buy C16H34V160 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for C16H34V160?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1 standards. Specific RoHS, REACH, and other compliance documentation is available from the manufacturer upon request.

MPN
C16H34V160