Skip to main content
Schneider Electric C16H47E100

Schneider Electric C16H47E100 ComPacT NSX160H, 100 A, 100 kA

MPN C16H47E100
Active

Schneider Electric, ComPacT NSX series, MCCB, C16H47E100, 100 A, 100 kA Icu at 240 V AC, 4P, MicroLogic 7.2 E trip unit.

$1,714.59 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C16H47E100 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C16H47E100 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical life cycles40000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C16H47E100 is a Schneider Electric ComPacT NSX160H moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 100 A at 40 °C. The 70 kA Icu at 415 V AC is the more common industrial rating; at 480 V AC it still holds 65 kA under UL 60947-4-1. The trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and R (earth-leakage) protection — all adjustable via the LCD display and toggle control. The 4-pole (4P) configuration with neutral on the left handles three-phase plus neutral distribution. The 35 mm connection pitch and front-facing upside/downside connections simplify panel wiring.

Deployment context

The 161 mm height, 140 mm width, and 86 mm depth fit standard distribution panel cutouts. The 0 to 2000 m operating altitude without derating covers most installations; above that, derate per the manufacturer's curve.

The IEC 60947-2 standard covers low-voltage switchgear and controlgear — specifically the breaking capacity and coordination requirements for MCCBs. Overvoltage category IV means it's suitable for main distribution panels at the service entrance. The electronic trip unit provides energy metering, time-stamped event histories, and demand current/power data via the LCD display.

MPN
C16H47E100