Schneider Electric C16H47E100 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C16H47E100 ComPacT NSX160H, 100 A, 100 kA

MPNC16H47E100
Active

Schneider Electric, ComPacT NSX series, MCCB, C16H47E100, 100 A, 100 kA Icu at 240 V AC, 4P, MicroLogic 7.2 E trip unit.

$1,714.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H47E100 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16H47E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (operating cycles)40000 cycles
C16H47E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX160H
C16H47E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C16H47E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C16H47E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C16H47E100 is a Schneider Electric ComPacT NSX160H moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 100 A at 40 °C. The 70 kA Icu at 415 V AC is the more common industrial rating; at 480 V AC it still holds 65 kA under UL 60947-4-1. The trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and R (earth-leakage) protection — all adjustable via the LCD display and toggle control. The 4-pole (4P) configuration with neutral on the left handles three-phase plus neutral distribution. The 35 mm connection pitch and front-facing upside/downside connections simplify panel wiring.

Deployment context

The 161 mm height, 140 mm width, and 86 mm depth fit standard distribution panel cutouts. The 0 to 2000 m operating altitude without derating covers most installations; above that, derate per the manufacturer's curve.

The IEC 60947-2 standard covers low-voltage switchgear and controlgear — specifically the breaking capacity and coordination requirements for MCCBs. Overvoltage category IV means it's suitable for main distribution panels at the service entrance. The electronic trip unit provides energy metering, time-stamped event histories, and demand current/power data via the LCD display.

Frequently asked questions

How do I get current pricing and availability for C16H47E100?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is C16H47E100's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What protection functions does the MicroLogic 7.2 E trip unit provide?

L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection, all adjustable via the LCD display.

What compliance documentation does this brand provide for C16H47E100?

The breaker is designed to EN/IEC 60947-2 and UL 60947-4-1 standards. Overvoltage category IV and pollution degree 3 per IEC 60664-1 are specified.

MPN