Schneider Electric C16N44V100

Schneider Electric C16N44V100 ComPacT NSX160N, 100A, 50kA 41

MPN C16N44V100
Active

Schneider Electric ComPacT NSX series, C16N44V100, 4-pole MCCB with MicroLogic 4.2 electronic trip unit, 100 A rating, 50 kA breaking capacity at 415 V AC.

$1,221.79 – $2,527.20 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C16N44V100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C16N44V100 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical life cycles40000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C16N44V100 is a ComPacT NSX160N moulded-case circuit breaker — a 4-pole, 100 A frame with an electronic MicroLogic 4.2 trip unit.

Trip unit and protection logic

The MicroLogic 4.2 is an electronic trip unit that provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection. The earth-leakage protection is integrated into the breaker — no external module needed. A 20-minute thermal memory means the breaker remembers a prior overload event and will trip faster on a reclose into a still-hot conductor, which is useful for motor or transformer feeders that see repeated starts.

Breaking capacity across voltages

The C16N44V100 is rated per EN/IEC 60947-2 with the following Icu: 90 kA at 220/240 V AC, 50 kA at 380/415 V AC, 50 kA at 440 V AC, 36 kA at 500 V AC, 35 kA at 525 V AC, and 10 kA at 660/690 V AC. It also carries UL 60947-4-1 ratings: 85 kA at 240 V AC, 50 kA at 480 V AC, and 10 kA at 600 V AC. The utilisation category is A — not intended for current-limiting applications, but suitable for general distribution and feeder protection where selectivity with downstream breakers is designed in.

Physical fit and mounting

Mounts on a backplate in horizontal or vertical orientation, flat on the back. Front connections on both upside and downside. Connection pitch is 35 mm. Neutral is on the left. IP40 protection — suitable for indoor panel installation; IK07 impact resistance.

Durability and operational life

Mechanical durability is 40,000 cycles. Electrical durability varies by load: 40,000 cycles at 440 V at half rated current (In/2), 20,000 cycles at 440 V at full In, 15,000 cycles at 690 V at In/2, and 7,500 cycles at 690 V at full In. These numbers matter for a breaker that sees frequent switching — like a main disconnect on a machine that cycles every shift.

MPN