Skip to main content
Schneider Electric C25F3MA220

C25F3MA220 ComPacT NSX 220A 3P Magnetic Motor Circuit Breake

MPN C25F3MA220
Active

Schneider Electric ComPacT NSX, circuit breaker, 220 A, 3P, MA magnetic trip unit, 85 kA Icu at 240 V AC, motor protection.

$575.20 – $1,336.50 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25F3MA220 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C25F3MA220 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

Motor protection breaker, 220 A, magnetic-only trip

That trip unit is designed for short-circuit protection only — no thermal overload — so it pairs with an external motor starter or overload relay for coordinated motor branch protection.

At 480 V AC it still holds 35 kA Icu (UL 60947-4-1), and at 600 V AC it derates to 15 kA. For a 480 V motor control center with an available fault current of 30 kA, that leaves headroom for full selectivity with downstream 18 kA breakers. The 22 kA Icu at 525 V AC covers 50 Hz industrial networks in regions that run 500 V class.

The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts. IP40 front face, IK07 impact rating.

MPN
C25F3MA220