Skip to main content
Schneider Electric C25N32D160

C25N32D160 ComPacT NSX250N Circuit Breaker, 160 A, MicroLogi

MPN C25N32D160
Active

Schneider Electric ComPacT NSX250N, C25N32D160, 3P circuit breaker, 160 A, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC.

$467.95 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25N32D160 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C25N32D160 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

160 A, MicroLogic 2.2, 50 kA at 415 V — the backbone of a distribution panel

The C25N32D160 is a Schneider Electric ComPacT NSX250N circuit breaker, 3-pole, rated 160 A at 40 °C with a MicroLogic 2.2 electronic trip unit. Its breaking capacity hits 50 kA Icu at 380/415 V AC (50/60 Hz) per IEC 60947-2 — the N-frame designation. The LED signalling on the front gives green for ready, red at 105 % Ir overload, orange at 90 % Ir — a quick visual for the panel walker.

The NSX250N frame delivers 90 kA Icu at 220/240 V AC, 50 kA at 380–440 V, 36 kA at 500 V, 35 kA at 525 V, and 10 kA at 660/690 V AC. For UL 60947-4-1 applications it's rated 85 kA at 240 V, 50 kA at 480 V, 15 kA at 600 V AC. On a 400 V system, that 50 kA covers most transformer secondary faults up to about 2 MVA.

Mounting and integration — backplate, front connections, IP40 enclosure

Mechanical durability is 20,000 cycles; electrical durability at 440 V In is 10,000 cycles, doubling to 20,000 at In/2. At 690 V In it drops to 5,000 cycles. For a main breaker that cycles once or twice a week, that's decades of service. For a frequently switched feeder, the 690 V electrical endurance is the limiting number.

MPN