Schneider Electric C25V36E250

Schneider Electric C25V36E250 ComPacT NSX250HB1, 250 A, 85 k

MPN C25V36E250
Active

Schneider Electric ComPacT NSX, NSX250HB1, 3P, 250 A at 40 °C, 85 kA Icu at 500 V AC, MicroLogic 6.2 E electronic trip unit, L,S,I,G protection, IP40, backplate mount.

$1,045.35 – $1,231.08 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25V36E250 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C

All specifications

C25V36E250 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C25V36E250 is a Schneider Electric ComPacT NSX250HB1 molded-case circuit breaker, 3-pole, rated 250 A at 40 °C. It carries an 85 kA Icu breaking capacity at 500 V AC 50/60 Hz per IEC 60947-2, which means it can safely interrupt a fault current up to that level without damage to itself or upstream gear — that's the rating that decides whether it holds on a high-fault panel or lets the arc flash through. The MicroLogic 6.2 E electronic trip unit provides four protection functions: L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault). That G function is the key difference from a standard thermal-magnetic breaker — it catches low-level ground faults that a magnetic trip might miss, which matters for equipment protection on distribution panels feeding sensitive loads.

Front connections top and bottom, which keeps wiring accessible and avoids reaching around the back. The LCD display on the trip unit shows energy metering, demand current, power quality, and time-stamped event logs — useful for commissioning and troubleshooting without needing a separate meter.

The 85 kA Icu at 500 V AC is the headline number, but the 75 kA at 690 V AC (HB1 code) is the one that governs if your system runs at higher voltage. Electrical durability is rated at 20,000 cycles at 440 V In/2, 10,000 cycles at 440 V In, and 5,000 cycles at 690 V In — so if this breaker sees frequent switching (like a motor disconnect), the 690 V figure is the endurance limit. That's a practical safety feature that a thermal-magnetic breaker doesn't have.

MPN