Skip to main content
Schneider Electric C25V46E250

Schneider Electric C25V46E250 ComPacT NSX 250A, 85kA 500V AC

MPN C25V46E250
Active

Schneider Electric ComPacT NSX, NSX250HB1, C25V46E250, 250 A rated, 85 kA Icu at 500 V AC, 4-pole, MicroLogic 6.2 E electronic trip unit.

$13.63 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25V46E250 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-40 °C

All specifications

C25V46E250 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It is a 4-pole, 250 A rated breaker designed for distribution applications, using an electronic MicroLogic 6.2 E trip unit that provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground fault) protection. The breaker is rated at 85 kA Icu at 500 V AC 50/60 Hz per IEC 60947-2, and carries a 75 kA Icu at 690 V AC — the HB1 breaking capacity code tells you it handles high fault currents at higher voltages. This is not a residential-grade breaker; it belongs in an industrial panel where selectivity and coordination matter.

The MicroLogic 6.2 E trip unit is fully electronic, so you can adjust the long-time pickup, short-time delay, and instantaneous settings to coordinate with downstream breakers — not a fixed thermal-magnetic curve. The 4-pole version (4P) with neutral on the left means it switches all four poles, including the neutral, which is required for some IT or corner-grounded delta systems.

The connection pitch is 35 mm, and both upside and downside connections are front-facing, which simplifies bus-bar or cable routing in a panel. The breaker is 161 mm high, 140 mm wide, and 86 mm deep, with an IK07 impact rating per IEC 62262 — tough enough for a panel environment but not for direct mechanical abuse.

Communication and metering

The MicroLogic 6.2 E trip unit includes an energy meter and communicates time-stamped histories, event tables, protection and alarm settings, maximeters/minimeters, instantaneous and demand values, power quality data, energy metering, demand current and power, and maintenance indicators. The LCD display on the front gives local readout without needing a separate meter or gateway — useful for a commissioning engineer checking load profiles or for an MRO planner verifying trip history after a fault.

MPN
C25V46E250