Skip to main content
Schneider Electric C25W36E160

Schneider Electric C25W36E160 ComPacT NSX 160A, 100kA 690V

MPN C25W36E160
Active

Schneider Electric ComPacT NSX, C25W36E160, 160 A at 40 °C, 100 kA Icu at 690 V AC, 3P, MicroLogic 6.2 E trip unit, EN/IEC 60947-2.

$1,045.41 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25W36E160 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C25W36E160 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

Part identification and key ratings

The C25W36E160 is a Schneider Electric ComPacT NSX moulded-case circuit breaker (MCCB) from the ComPacT range, rated 160 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. It carries a 100 kA Icu breaking capacity at 690 V AC 50/60 Hz per EN/IEC 60947-2 — that is the maximum short-circuit current it can safely interrupt without damage, making it suitable for high-fault-level distribution panels. The 3-pole (3P) configuration and 160 A frame cover main feeder or large sub-feed applications in commercial and industrial switchboards.

Trip unit and protection logic

The MicroLogic 6.2 E provides four protection functions: L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground-fault). The electronic trip unit enables adjustable curves and coordination selectivity — critical for a distribution board where a downstream fault must not take out the upstream breaker. The 20-minute thermal memory before and after tripping ensures the breaker's thermal model tracks the real conductor heating, so re-energising a hot circuit does not miss a second overload event.

Durability and environmental ratings

Mechanical durability is rated at 20,000 cycles; electrical durability at 440 V In (10,000 cycles) and 690 V In (5,000 cycles). The IP40 enclosure protection (IK07 impact) suits installation in a clean, dry switchboard — not a washdown environment. Operating altitude extends to 2000 m without derating, and up to 5000 m with derating applied.

Metering and communication capability

The MicroLogic 6.2 E trip unit includes an energy meter and communicates power quality, energy metering, instantaneous and demand values, maintenance indicators, protection and alarm settings, time-stamped histories, and demand current/power maximeters/minimeters. This data can be read locally via the LCD display or integrated into a building management system through optional communication modules, supporting energy monitoring and predictive maintenance without additional metering hardware.

MPN
C25W36E160