Skip to main content
Schneider Electric C25W36E160 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C25W36E160 ComPacT NSX 160A, 100kA 690V

MPNC25W36E160
Obsolete

Schneider Electric ComPacT NSX, C25W36E160, 160 A at 40 °C, 100 kA Icu at 690 V AC, 3P, MicroLogic 6.2 E trip unit, EN/IEC 60947-2.

$1,045.41Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25W36E160 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25W36E160 — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25W36E160 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX250HB2
C25W36E160 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25W36E160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25W36E160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Part identification and key ratings

The C25W36E160 is a Schneider Electric ComPacT NSX moulded-case circuit breaker (MCCB) from the ComPacT range, rated 160 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. It carries a 100 kA Icu breaking capacity at 690 V AC 50/60 Hz per EN/IEC 60947-2 — that is the maximum short-circuit current it can safely interrupt without damage, making it suitable for high-fault-level distribution panels. The 3-pole (3P) configuration and 160 A frame cover main feeder or large sub-feed applications in commercial and industrial switchboards.

Trip unit and protection logic

The MicroLogic 6.2 E provides four protection functions: L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground-fault). The electronic trip unit enables adjustable curves and coordination selectivity — critical for a distribution board where a downstream fault must not take out the upstream breaker. The 20-minute thermal memory before and after tripping ensures the breaker's thermal model tracks the real conductor heating, so re-energising a hot circuit does not miss a second overload event.

Durability and environmental ratings

Mechanical durability is rated at 20,000 cycles; electrical durability at 440 V In (10,000 cycles) and 690 V In (5,000 cycles). The IP40 enclosure protection (IK07 impact) suits installation in a clean, dry switchboard — not a washdown environment. Operating altitude extends to 2000 m without derating, and up to 5000 m with derating applied.

Metering and communication capability

The MicroLogic 6.2 E trip unit includes an energy meter and communicates power quality, energy metering, instantaneous and demand values, maintenance indicators, protection and alarm settings, time-stamped histories, and demand current/power maximeters/minimeters. This data can be read locally via the LCD display or integrated into a building management system through optional communication modules, supporting energy monitoring and predictive maintenance without additional metering hardware.

Frequently asked questions

What is the breaking capacity of C25W36E160?

The C25W36E160 has a breaking capacity of 100 kA Icu at 500 V AC, 525 V AC, and 660/690 V AC 50/60 Hz per EN/IEC 60947-2.

What protection functions does the MicroLogic 6.2 E trip unit provide?

The MicroLogic 6.2 E trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and G (ground-fault) protection.

What is the rated current of C25W36E160?

The rated current is 160 A at 40 °C.

Where can I buy C25W36E160 and how is it quoted?

The C25W36E160 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

MPN
C25W36E160