Skip to main content
Schneider Electric C25W36E250

Schneider Electric C25W36E250 ComPacT NSX 250A, 100kA at 690

MPN C25W36E250
Obsolete

Schneider Electric ComPacT NSX, NSX250HB2, 3P, 250 A at 40 °C, MicroLogic 6.2 E trip unit, 100 kA Icu at 690 V AC, IP40, toggle control, LCD display.

$1,045.35 – $1,221.84 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25W36E250 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C25W36E250 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C25W36E250 is a ComPacT NSX moulded-case circuit breaker (MCCB) from the NSX250HB2 family, rated 250 A at 40 °C with a MicroLogic 6.2 E electronic trip unit. It's a 3-pole unit built for distribution applications, with a 100 kA Icu breaking capacity at 690 V AC 50/60 Hz per IEC 60947-2 — that's the fault-clearing rating that tells you it can handle high-fault-current industrial feeds without upstream coordination headaches. The trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous), and G (ground-fault) protection, all configurable via the front LCD display and toggle controls.

Communication and metering capability

The MicroLogic 6.2 E trip unit includes an energy meter and communicates power quality data, demand current, instantaneous and demand values, protection and alarm settings, energy metering, maintenance indicators, and time-stamped event histories. That makes it more than a simple overcurrent protector — it feeds panel-level energy data back to a BMS or SCADA system without an external metering module. Five accessory slots are available for additional communication or aux contact modules.

Environmental and installation limits

Operating altitude is 0–2000 m without derating, 2000–5000 m with derating. Relative humidity range is 0–95 %.

Durability and mechanical life

Electrical durability varies with load: 20,000 cycles at 440 V at half rated current, 10,000 cycles at 440 V at full rated current, 10,000 cycles at 690 V at half rated current, and 5,000 cycles at 690 V at full rated current. That's typical for a distribution MCCB — not a switching device for frequent motor starts, but fine for infrequent isolation and fault protection.

MPN