Schneider Electric C40F42D400

Schneider C40F42D400 ComPacT NSX 400A 4P MCCB, 40 kA

MPN C40F42D400
Active

Schneider Electric ComPacT NSX series, C40F42D400, 400 A 4P MCCB, MicroLogic 2.3 electronic trip unit, 40 kA Icu at 240 V AC, toggle control, backplate mount.

$875.96 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C40F42D400 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C40F42D400 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width185 mm
Height255 mm
Electrical life cycles12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

It is rated for distribution applications on AC networks at 50/60 Hz, with a breaking capacity of 40 kA Icu at 240 V AC (IEC 60947-2) and 36 kA at 415 V AC. The 400 A rating at 40 °C makes this breaker a fit for large feeder or main-switch duty in commercial and industrial panels where upstream fault current is high enough to demand the 40 kA interrupt rating at 240 V.

The breaker complies with EN/IEC 60947-2, carries an IK07 impact rating, and is rated IP40 for the enclosure.

The 185 mm width and 255 mm height fit standard switchgear cubicle cutouts; the 110 mm depth leaves clearance for rear-connected busbars or cable lugs. The toggle control provides manual on/off/tripped indication. Neutral is on the left (4P configuration). Six accessory slots are available for shunt trips, auxiliary contacts, or motor operators.

The full Icu curve: 40 kA at 240 V, 36 kA at 415 V, 30 kA at 440 V, 25 kA at 500 V, 20 kA at 525 V, and 10 kA at 690 V. Under UL 60947-4-1, ratings are 85 kA at 240 V, 35 kA at 480 V, and 20 kA at 600 V. Selectivity with downstream breakers can be achieved using the short-time delay on the MicroLogic 2.3 trip unit. Electrical endurance is 12,000 cycles at 440 V at half rated current, 6,000 cycles at full rated current; mechanical endurance is 15,000 cycles.

MPN
C40F42D400