Skip to main content
Schneider Electric C40H47E400

Schneider Electric C40H47E400 ComPacT NSX400H, 400 A, 100 kA

MPN C40H47E400
Obsolete

Schneider Electric ComPacT NSX, NSX400H, 400 A, 100 kA Icu at 240 V AC, MicroLogic 7.3 E trip unit, 4P, EN/IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C40H47E400 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C40H47E400 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth110 mm
Width185 mm
Height255 mm
Electrical life cycles12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical life cycles15000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

400 A electronic-trip MCCB with earth-leakage and metering

The Schneider Electric C40H47E400 is a ComPacT NSX400H 4-pole moulded-case circuit breaker with a MicroLogic 7.3 E electronic trip unit rated 400 A at 40 °C. The trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection, making it suitable for distribution applications where ground-fault detection is required alongside overcurrent protection. The H breaking capacity code delivers 70 kA Icu at 415 V AC, 100 kA Icu at 240 V AC, and 65 kA Icu at 480 V AC — figures that govern fault-clearing capability at the service-entrance or main switchboard level.

Above that, the electronic trip unit applies an I²t curve for overloads and a fixed-time S curve for short-time faults, with earth-leakage (R) protection adjustable via the IΔn rotary switch. At 690 V AC the Icu drops to 20 kA, so the voltage at the fault point must be confirmed when specifying for 600 V class systems. The MicroLogic 7.3 E also logs time-stamped events, energy metering, and power quality data, which feeds into a building management system without a separate power meter.

At 255 mm high, 185 mm wide, and 110 mm deep, it occupies a standard MCCB footprint in a distribution panel. The 45 mm connection pitch matches common busbar and lug kits. The toggle control and LCD display are accessible from the front, and the six accessory slots accept auxiliary contacts, shunt trips, or communication modules without increasing the panel cutout.