Skip to main content
Schneider Electric C40H47E400 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C40H47E400 ComPacT NSX400H, 400 A, 100 kA

MPNC40H47E400
Obsolete

Schneider Electric ComPacT NSX, NSX400H, 400 A, 100 kA Icu at 240 V AC, MicroLogic 7.3 E trip unit, 4P, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40H47E400 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40H47E400 — Electrical Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (operating cycles)15000 cycles
C40H47E400 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX400H
C40H47E400 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C40H47E400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C40H47E400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

400 A electronic-trip MCCB with earth-leakage and metering

The Schneider Electric C40H47E400 is a ComPacT NSX400H 4-pole moulded-case circuit breaker with a MicroLogic 7.3 E electronic trip unit rated 400 A at 40 °C. The trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection, making it suitable for distribution applications where ground-fault detection is required alongside overcurrent protection. The H breaking capacity code delivers 70 kA Icu at 415 V AC, 100 kA Icu at 240 V AC, and 65 kA Icu at 480 V AC — figures that govern fault-clearing capability at the service-entrance or main switchboard level.

Above that, the electronic trip unit applies an I²t curve for overloads and a fixed-time S curve for short-time faults, with earth-leakage (R) protection adjustable via the IΔn rotary switch. At 690 V AC the Icu drops to 20 kA, so the voltage at the fault point must be confirmed when specifying for 600 V class systems. The MicroLogic 7.3 E also logs time-stamped events, energy metering, and power quality data, which feeds into a building management system without a separate power meter.

At 255 mm high, 185 mm wide, and 110 mm deep, it occupies a standard MCCB footprint in a distribution panel. The 45 mm connection pitch matches common busbar and lug kits. The toggle control and LCD display are accessible from the front, and the six accessory slots accept auxiliary contacts, shunt trips, or communication modules without increasing the panel cutout.

Frequently asked questions

How do I get current pricing and availability for C40H47E400?

The C40H47E400 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm landed-cost figure.

What is C40H47E400's listed breaking capacity at 415 V AC?

The C40H47E400 delivers 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2, and 65 kA Icu at 480 V AC conforming to UL 60947-4-1.

What compliance documentation does Schneider provide for C40H47E400?

The C40H47E400 is certified to EN/IEC 60947-2 and UL 60947-4-1. A declaration of conformity and CE/UKCA documentation are available with the shipment.

MPN