Skip to main content
Schneider Electric C63F3

Schneider Electric C63F3 ComPacT NSX630F Basic Frame, 630A,

MPN C63F3
Active

Schneider Electric ComPacT NSX630F basic frame, C63F3, 630 A at 40 °C, 36 kA Icu at 415 VAC, 3 poles, without trip unit.

$599.12 – $836.99 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C63F3 key specifications
ParameterValue
Control typeToggle
Protection typeWithout protection
Main product or component typeBasic frame
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch45 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C63F3 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth110 mm
Width140 mm
Height255 mm
Electrical life cycles6000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 8000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical life cycles15000 cycles conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-25...70 °C

Product details

What this basic frame is and what it needs

The C63F3 is a ComPacT NSX630F basic frame — a 3-pole, 630 A molded-case switch housing with no trip unit fitted. You select and install a separate trip unit (electronic or thermal-magnetic) to define the protection curve. The frame carries a 36 kA Icu at 415 VAC and an 85 kA breaking capacity at 240 VAC per UL 508, so it handles high-fault service-entrance or distribution positions where the trip unit is specified later.

At 240 VAC the frame clears 85 kA (UL 508); at 480 VAC it clears 35 kA (UL 508); at 600 VAC it clears 20 kA (UL 508). Under IEC 60947-2 the Icu values are 40 kA at 220/240 VAC, 36 kA at 380/415 VAC, 30 kA at 440 VAC, 25 kA at 500 VAC, 20 kA at 525 VAC, and 10 kA at 660/690 VAC.

The frame mounts fixed to a backplate (not DIN rail). Connection pitch is 45 mm. Both line and load connections are front-access, which simplifies busbar or cable routing in a panel where the breaker is mounted in a row. The front face carries Class II electrical shock protection, so no additional insulation cover is required on the operator side. IP40 enclosure protection keeps out tools and small debris; IK07 impact resistance handles incidental contact during panel work.

The C63F3 is designed and certified to EN/IEC 60947-2 (low-voltage switchgear and controlgear) and UL 60947-4-1 (contactors and motor-starters). Overvoltage category III suits fixed-installation distribution boards. The manufacturer provides the standard declaration of conformity and UL recognition documentation with the shipment.

MPN