ENW13202 key specifications
ParameterValue
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C

All specifications

ENW13202 additional specifications
ParameterValue
Pollution degreeclass 3
Depth277 mm
Width288 mm
Height322 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW13202 is an EasyPact NW drawout circuit breaker rated 800 A at 40 °C, with a 66 kA Icu breaking capacity at 220-440 V AC 50/60 Hz per IEC 60947-2. The 55 kA Ics service breaking capacity tells you it can clear a fault and be reclosed without maintenance, which matters for continuous-process lines where a nuisance trip can't wait for a breaker swap.

Drawout mounting and panel integration

This breaker mounts on a rail base plate with a drawout mechanism — the 277 mm depth and 288 mm width fit standard switchgear cubicles. Rear horizontal or vertical connection positions give flexibility for busbar routing. The 70 mm connection pitch without spreader matches common busbar drilling patterns.

Key ratings and standards

Rated insulation voltage 1000 V AC, impulse withstand 12 kV. Short-time withstand current 50 kA for 1 s — that's the thermal limit for a delayed trip coordination study. Making capacity 75 kA Icm. Maximum breaking time 35 ms, closing time 70 ms. IP30 protection — indoor panel use only, not for washdown environments.