The Schneider Electric ENW13202 is an EasyPact NW drawout circuit breaker rated 800 A at 40 °C, with a 66 kA Icu breaking capacity at 220-440 V AC 50/60 Hz per IEC 60947-2. The 55 kA Ics service breaking capacity tells you it can clear a fault and be reclosed without maintenance, which matters for continuous-process lines where a nuisance trip can't wait for a breaker swap.
Drawout mounting and panel integration
This breaker mounts on a rail base plate with a drawout mechanism — the 277 mm depth and 288 mm width fit standard switchgear cubicles. Rear horizontal or vertical connection positions give flexibility for busbar routing. The 70 mm connection pitch without spreader matches common busbar drilling patterns.
Key ratings and standards
Rated insulation voltage 1000 V AC, impulse withstand 12 kV. Short-time withstand current 50 kA for 1 s — that's the thermal limit for a delayed trip coordination study. Making capacity 75 kA Icm. Maximum breaking time 35 ms, closing time 70 ms. IP30 protection — indoor panel use only, not for washdown environments.