Skip to main content
Schneider Electric ENW13286

ENW13286 EasyPact NW Switch Disconnector, 1250 A, 3P

MPN ENW13286
Active

Schneider Electric EasyPact NW series, ENW13286 switch disconnector, 1250 A, 3 poles, AC-23A, 440 V AC, fixed mounting, rear connection.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13286 key specifications
ParameterValue
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1250 A AC 50/60 Hz 440 V
Utilization categoryAC-23 A
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C without control unit

All specifications

ENW13286 additional specifications
ParameterValue
Pollution degreeclass 3
Depth196 mm
Width346 mm
Height301 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Switch disconnector for distribution — 1250 A, AC-23A duty

The Schneider Electric ENW13286 is a 3-pole switch disconnector from the EasyPact NW range, rated 1250 A operational current in AC-23A utilisation category at 440 V AC. It is certified for isolation per IEC 60947-3, meaning it provides visible-break isolation when the contact position indicator shows open.

Mounting and connection — fixed base plate, rear terminals

Fixed mounting on a rail base plate. Connection pitch is 70 mm without spreader, and the rear-located terminals accept vertical or horizontal cable entry. Dimensions are 346 mm wide × 301 mm high × 196 mm deep — check the gland-plate layout before cutting the back panel. IP30 protection keeps fingers out but expects a cabinet door.

Withstand and making capacity — fault-current handling

Rated short-time withstand current (Icw) is 50 kA for 1 second at 220–440 V — that is the current the switch can carry without damage during a fault while the upstream breaker clears. Rated short-circuit making capacity (Icm) is 75 kA at the same voltage. Insulation voltage (Ui) is 1000 V AC, so the switch can sit on a 690 V bus without derating the insulation system.

MPN