Skip to main content
Schneider Electric ENW21413

ENW21413 EasyPac NW Trip System 2.0E, 800-4000 A

MPN ENW21413
Active

Schneider Electric EasyPact NW, Trip System 2.0E, control unit ENW21413, drawout, 800-4000 A, 690 V AC, LI protection.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW21413 specifications
ParameterValue
Display typeDigital display
Trip unit typeMicro-processor based
Main product or component typeControl unit
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Temp storage max85 °C
Temp storage min-25 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-25...85 °C
Depth75 mm
Width55 mm
Height200 mm
Operating temperature-5...70 °C

Product details

Trip unit for EasyPact NW drawout breakers

The ENW21413 is a Trip System 2.0E microprocessor-based control unit for Schneider Electric EasyPact NW drawout circuit breakers. It provides LI protection — long-time overload and instantaneous short-circuit — with an adjustable trip unit rating from 800 to 4000 A, making it the brains for large industrial power distribution on 690 V AC networks at 50/60 Hz.

Protection settings and coordination

Long-time pickup (Ir) adjusts from 0.4 to 1 x In across nine settings, with a corresponding delay (Tr) adjustable from 0.5 to 24 seconds at 6 x Ir. Instantaneous pickup (Ii) spans 1.5 to 10 x Ir, also in nine steps. This granularity lets you shape the trip curve to the load — motor starts, transformer inrush, or feeder protection — without swapping the unit. Zone selective interlocking (ZSI) is built in, so downstream faults clear at the closest breaker while upstream units hold — reduces arc-flash energy and keeps healthy feeders online. Thermal memory tracks the last 20 minutes of heating and cooling before and after a trip, preventing nuisance reclose on a still-hot conductor.

Drawout mounting and panel integration

The drawout mounting mode means this control unit slides into the EasyPact NW cradle — no hardwiring the trip unit itself. Physical footprint is 200 mm high, 55 mm wide, 75 mm deep. The digital display shows fault type (overload, short-circuit, earth fault, internal fault) and energy metering data, so a panel walk-down reads the event log without a laptop.

MPN
ENW21413