ENW24101 EasyPact NW Circuit Breaker, 800 A, 50 kA

MPN ENW24101
Active

Schneider Electric EasyPact NW ENW08N frame, circuit breaker, 3P, 800 A at 40 °C, 50 kA Icu at 440 V AC, drawout mount, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24101 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...60 °C

Product details

What this 800 A drawout breaker does for your main

The ENW24101 is a Schneider Electric EasyPact NW circuit breaker on the ENW08N frame — a three-pole, 800 A drawout unit built for distribution duty. That 800 A rating at 40 °C tells you it handles full continuous current in a warm switchroom without derating; push it to 60 °C and you'll need to knock the ampacity down per the thermal curve.

Drawout mount, rear connection — panel integration

Drawout mounting means the breaker slides into a cradle, so you can rack it out for maintenance or replacement without pulling the bus bars. Rear connection keeps the power cables out of the front of the panel — cleaner layout, less clutter for the guy wiring the control transformer. The 115 mm connection pitch without spreader sets the bus spacing; if you're retrofitting into an existing lineup, measure that pitch before ordering the adapter kit. IP40 keeps tools and fingers out but isn't rated for washdown — keep it indoors.

What the standards and durability numbers mean

Compliant with IEC 60947-2, the standard for low-voltage circuit breakers — that's the spec that defines the Icu, Ics, and Icw ratings, so you know the test protocol behind the numbers. Mechanical durability is 20,000 cycles with maintenance, 10,000 without; electrical durability is 6,000 cycles at 440 V without maintenance. That's not a daily-switch duty cycle — it's a main breaker that cycles on fault or maintenance, not a contactor running every minute.