Skip to main content
Schneider Electric ENW24142

Schneider Electric ENW24142 EasyPact NW Circuit Breaker, 100

MPN ENW24142
Active

Schneider Electric EasyPact NW circuit breaker, ENW24142, 1000 A, 66 kA Icu, 3P, IP40, fixed mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24142 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24142 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width422 mm
Height352 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

What you're looking at

Schneider Electric ENW24142 is a fixed-mount EasyPact NW air circuit breaker rated 1000 A at 40 °C, 3-pole, with a 66 kA Icu breaking capacity at 220...440 V AC. The IP40 enclosure keeps tools and fingers out but isn't sealed against water; this lives in a dry switchgear lineup, not a washdown area.

Breaking capacity — the number that matters for fault coordination

That 1 kA gap between Icu and Ics is tight, typical of a high-performance air breaker. For selectivity studies, the Icw short-time withstand is 65 kA for 1 s at 440 V, so downstream breakers have time to clear before this one trips on a delayed curve.

The ENW24142 is current production. For a 1000 A frame breaker still in the catalog, the supply channel is standard.

Fixed mount on a base plate, rear-connected. The connection pitch is 115 mm without a spreader, so busbar drilling and cable lug spacing need to match that dimension. Horizontal or vertical connection position is allowed — useful for tight cabinet layouts. Dimensions: 422 mm wide, 352 mm high, 297 mm deep. That depth includes the rear connection space, so account for it in the enclosure depth.

Isolation and endurance

Electrical endurance at 440 V is 6,000 cycles without maintenance — enough for a distribution feeder that sees a few operations per year, not a motor-switching duty cycle.

MPN
ENW24142