Skip to main content
Schneider Electric ENW24145

ENW24145 EasyPact NW Circuit Breaker, 2000 A, 66 kA Icu

MPN ENW24145
Active

Schneider Electric EasyPact NW, ENW24145, 3P circuit breaker, 2000 A at 40 °C, 66 kA Icu at 440 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24145 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24145 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width422 mm
Height352 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24145 is a fixed-mount, 3-pole EasyPact NW air circuit breaker rated for 2000 A at 40 °C. It's built for distribution duty in industrial switchboards and main feeders where you need high current handling and serious fault interruption. The 66 kA Icu at 220...440 V AC (50/60 Hz) per IEC 60947-2 means it can safely clear a bolted fault up to that level without welding contacts or venting plasma into the enclosure — that's the kind of rating that decides whether the upstream transformer breaker holds or the whole substation trips.

That's the number you size your bus bars and cable terminations to. At 690 V the Icu drops to 50 kA, still substantial for industrial distribution. Rated insulation voltage is 1000 V AC, operational voltage 690 V AC. Impulse withstand is 12 kV, which covers most installation categories in industrial environments. Electrical endurance at 440 V is 6,000 cycles Category B without maintenance. That's a lot of switching for a breaker this size — it's not just a passive disconnect; it can handle routine switching of the feeder if your process requires it.

Dimensions are 422 mm wide, 352 mm high, 297 mm deep. That depth is the critical one for enclosure depth selection — make sure your cabinet door clears the breaker face and any auxiliary devices mounted on it.

MPN