Skip to main content
Schneider Electric ENW24145 — Air Circuit Breakers

ENW24145 EasyPact NW Circuit Breaker, 2000 A, 66 kA Icu

MPNENW24145
Active

Schneider Electric EasyPact NW, ENW24145, 3P circuit breaker, 2000 A at 40 °C, 66 kA Icu at 440 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24145 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24145 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24145 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24145 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24145 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24145 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24145 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24145 is a fixed-mount, 3-pole EasyPact NW air circuit breaker rated for 2000 A at 40 °C. It's built for distribution duty in industrial switchboards and main feeders where you need high current handling and serious fault interruption. The 66 kA Icu at 220...440 V AC (50/60 Hz) per IEC 60947-2 means it can safely clear a bolted fault up to that level without welding contacts or venting plasma into the enclosure — that's the kind of rating that decides whether the upstream transformer breaker holds or the whole substation trips.

That's the number you size your bus bars and cable terminations to. At 690 V the Icu drops to 50 kA, still substantial for industrial distribution. Rated insulation voltage is 1000 V AC, operational voltage 690 V AC. Impulse withstand is 12 kV, which covers most installation categories in industrial environments. Electrical endurance at 440 V is 6,000 cycles Category B without maintenance. That's a lot of switching for a breaker this size — it's not just a passive disconnect; it can handle routine switching of the feeder if your process requires it.

Dimensions are 422 mm wide, 352 mm high, 297 mm deep. That depth is the critical one for enclosure depth selection — make sure your cabinet door clears the breaker face and any auxiliary devices mounted on it.

Frequently asked questions

What is the breaking capacity of ENW24145?

66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The service breaking capacity (Ics) is 65 kA at 220...440 V.

What standards does ENW24145 comply with?

It is designed and tested to IEC 60947-2 for circuit breakers. Pollution degree 4 per IEC 60664-1. Suitable for isolation per IEC 60947-2.

Where can I buy ENW24145 and how is it quoted?

We source ENW24145 through independent distribution channels. Submit an RFQ for a firm price and current lead time; availability is confirmed at quote time.

MPN