Skip to main content
Schneider Electric ENW24154

ENW24154 EasyPact NW Circuit Breaker, 2500 A, 66 kA

MPN ENW24154
Active

Schneider Electric EasyPact NW, ENW24154 circuit breaker, 2500 A at 40 °C, 66 kA Icu at 440 V AC, 4P, drawout, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24154 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24154 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

EasyPact NW drawout — 2500 A, 66 kA at 440 V

The Schneider Electric ENW24154 is an EasyPact NW 4-pole drawout circuit breaker rated for 2500 A at 40 °C, with a breaking capacity of 66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, all per IEC 60947-2. The drawout mounting lets you rack the breaker out for maintenance or replacement without pulling the bus bars, which saves hours of downtime on a live panel.

The 1000 V rated insulation voltage (Ui) and 690 V operational voltage (Ue) cover common low-voltage distribution voltages up to 690 V line-to-line.

Integration into the switchboard

Drawout mounting on rails — the breaker slides into a cradle with rear horizontal or vertical connections. The 4-pole configuration (4P 4d) with neutral on the left means it can be set for 3D (no neutral protection), 3D + N/2 (half-rated neutral), or 4D (full neutral protection). Connection pitch is 115 mm without a spreader. The IP40 enclosure protection keeps fingers and tools out but is not sealed against water — install in a dry indoor switchboard. Dimensions: 556 mm wide, 439 mm high, 395 mm deep — plan the cubicle depth accordingly.

MPN
ENW24154