Schneider Electric ENW24154 — Air Circuit Breakers

ENW24154 EasyPact NW Circuit Breaker, 2500 A, 66 kA

MPNENW24154
Active

Schneider Electric EasyPact NW, ENW24154 circuit breaker, 2500 A at 40 °C, 66 kA Icu at 440 V AC, 4P, drawout, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24154 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24154 — Electrical ratings
ParameterValue
Rated current (In)2500 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24154 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24154 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24154 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24154 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24154 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

EasyPact NW drawout — 2500 A, 66 kA at 440 V

The Schneider Electric ENW24154 is an EasyPact NW 4-pole drawout circuit breaker rated for 2500 A at 40 °C, with a breaking capacity of 66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, all per IEC 60947-2. The drawout mounting lets you rack the breaker out for maintenance or replacement without pulling the bus bars, which saves hours of downtime on a live panel.

The 1000 V rated insulation voltage (Ui) and 690 V operational voltage (Ue) cover common low-voltage distribution voltages up to 690 V line-to-line.

Integration into the switchboard

Drawout mounting on rails — the breaker slides into a cradle with rear horizontal or vertical connections. The 4-pole configuration (4P 4d) with neutral on the left means it can be set for 3D (no neutral protection), 3D + N/2 (half-rated neutral), or 4D (full neutral protection). Connection pitch is 115 mm without a spreader. The IP40 enclosure protection keeps fingers and tools out but is not sealed against water — install in a dry indoor switchboard. Dimensions: 556 mm wide, 439 mm high, 395 mm deep — plan the cubicle depth accordingly.

Frequently asked questions

What is the breaking capacity of ENW24154?

66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The service breaking capacity Ics is 65 kA at 220...440 V and 50 kA at 690 V.

How do I set the neutral protection on this breaker?

The 4-pole breaker allows three settings: 3D (no neutral protection), 3D + N/2 (neutral protection at half the rated current), or 4D (full neutral protection). The neutral pole is on the left side.

MPN