Skip to main content
Schneider Electric ENW24157

Schneider Electric ENW24157 EasyPact NW Circuit Breaker, 800

MPN ENW24157
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24157, 800 A at 40 °C, 66 kA Icu at 440 V AC, 4 poles, IP40, fixed mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24157 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24157 is a fixed-mount EasyPact NW air circuit breaker rated 800 A at 40 °C, built for distribution duty in industrial switchboards. It carries a 66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2, so it clears high fault currents without upstream coordination issues. The 4-pole design with left-side neutral and rear vertical/horizontal connections suits main or tie-breaker positions in low-voltage switchgear.

That 65 kA Ics / 66 kA Icu ratio (98 %) is high, typical of Category B breakers that are expected to remain in service after a fault. The 690 V operational voltage (Ue) and 1000 V insulation voltage (Ui) confirm it handles 690 V line-to-line systems common in heavy industrial plants.

Fixed mount on a base plate — no DIN rail, so panel cutouts and bolt patterns need to match the 537 mm width, 352 mm height, and 297 mm depth. Rear connection with a 115 mm connection pitch without spreader means busbar or cable terminations must follow that spacing. IP40 enclosure protection keeps out tools and fingers but not water; install inside a switchboard or enclosure rated for the environment. Pollution degree 4 per IEC 60664-1 means the breaker is designed for continuous conductive contamination (dust, condensation) — typical for unsealed industrial switchgear rooms.

Certified to IEC 60947-2 for low-voltage switchgear and controlgear. Isolation suitable per that standard — the breaker provides visible isolation when open. Pollution degree 4, ambient operation from -5 to 60 °C, storage from -40 to 85 °C. The 4 protected poles (4P 4d) with selectable neutral protection (no protection, 0.5× Ir, or 1× Ir) cover solidly-grounded and impedance-grounded systems.

MPN