Skip to main content
Schneider Electric ENW24175

Schneider EasyPact NW ENW24175 Switch Disconnector, 1250 A,

MPN ENW24175
Active

Schneider Electric EasyPact NW range, ENW24175 switch disconnector, 1250 A AC-23A, 690 V AC, 3 poles, fixed mounting, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24175 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1250 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24175 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width422 mm
Height352 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Switch disconnector for distribution, 1250 A AC-23A

The Schneider Electric ENW24175 is a fixed-mount switch disconnector from the EasyPact NW range, rated 1250 A in AC-23A utilisation category at 690 V AC — meaning it handles the high inrush of motor loads or mixed resistive-inductive circuits on distribution boards, not just resistive heating banks. The 3-pole unit is designed for isolation duty (IEC 60947-3 certified) with a visible contact position indicator, so it doubles as a service-disconnect for downstream maintenance without relying on a separate lockout device. Rated insulation voltage sits at 1000 V AC, with a 12 kV impulse withstand — this covers 690 V line-to-line systems plus the transient spikes from nearby lightning or capacitor bank switching. The short-time withstand current is 50 kA for 1 second (25 kA for 3 seconds), and the making capacity reaches 105 kA peak at 50/60 Hz, which defines its fault-closing capability for coordination studies on high-fault panels. The IP40 enclosure keeps tools and fingers out but is not washdown-rated; it expects a cabinet or panel cover for outdoor installation.

Mounting and connection

Fixed base-plate mounting, rear connection. The 422 mm width by 352 mm height by 297 mm depth footprint needs a panel backplate sized to clear the rear terminals and allow a 115 mm connection pitch without spreader bars. Horizontal or vertical cable entry is possible, but all terminations are rear-access — plan gland-plate layout accordingly.

Electrical endurance is 6000 cycles at 440 V AC-23A and 4000 cycles at 690 V AC-23A without maintenance. Mechanical durability is 20000 cycles with maintenance, 10000 without. For a distribution disconnect that sees infrequent operation (a few times a week), that is a long service life; for a machine disconnect cycled multiple times per shift, derate or consider a contactor-based solution.

MPN