Skip to main content
Schneider Electric ENW24175 — Air Circuit Breakers

Schneider EasyPact NW ENW24175 Switch Disconnector, 1250 A,

MPNENW24175
Active

Schneider Electric EasyPact NW range, ENW24175 switch disconnector, 1250 A AC-23A, 690 V AC, 3 poles, fixed mounting, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ENW24175 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW24175 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1250 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3
ENW24175 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz
ENW24175 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A
ENW24175 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
ENW24175 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
ENW24175 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

Switch disconnector for distribution, 1250 A AC-23A

The Schneider Electric ENW24175 is a fixed-mount switch disconnector from the EasyPact NW range, rated 1250 A in AC-23A utilisation category at 690 V AC — meaning it handles the high inrush of motor loads or mixed resistive-inductive circuits on distribution boards, not just resistive heating banks. The 3-pole unit is designed for isolation duty (IEC 60947-3 certified) with a visible contact position indicator, so it doubles as a service-disconnect for downstream maintenance without relying on a separate lockout device. Rated insulation voltage sits at 1000 V AC, with a 12 kV impulse withstand — this covers 690 V line-to-line systems plus the transient spikes from nearby lightning or capacitor bank switching. The short-time withstand current is 50 kA for 1 second (25 kA for 3 seconds), and the making capacity reaches 105 kA peak at 50/60 Hz, which defines its fault-closing capability for coordination studies on high-fault panels. The IP40 enclosure keeps tools and fingers out but is not washdown-rated; it expects a cabinet or panel cover for outdoor installation.

Mounting and connection

Fixed base-plate mounting, rear connection. The 422 mm width by 352 mm height by 297 mm depth footprint needs a panel backplate sized to clear the rear terminals and allow a 115 mm connection pitch without spreader bars. Horizontal or vertical cable entry is possible, but all terminations are rear-access — plan gland-plate layout accordingly.

Electrical endurance is 6000 cycles at 440 V AC-23A and 4000 cycles at 690 V AC-23A without maintenance. Mechanical durability is 20000 cycles with maintenance, 10000 without. For a distribution disconnect that sees infrequent operation (a few times a week), that is a long service life; for a machine disconnect cycled multiple times per shift, derate or consider a contactor-based solution.

Frequently asked questions

What is the AC-23A rating and why does it matter?

The 1250 A AC-23A rating at 690 V means this switch disconnector is rated for switching motor loads or mixed loads with high inrush current, not just resistive heating. AC-23A is a higher-duty category than AC-21 or AC-22, so it handles the inductive kick from motors and transformers during normal switching.

What is the short-circuit withstand of ENW24175?

The rated short-time withstand current is 50 kA for 1 second or 25 kA for 3 seconds at -5 to 70 °C, and the rated short-circuit making capacity is 105 kA peak at 50/60 Hz. These figures are needed for selective coordination studies on distribution boards.

What compliance standards does ENW24175 meet?

It is designed and tested to IEC 60947-3 for switch-disconnectors and IEC 60664-1 for insulation coordination at pollution degree 4. The suitability-for-isolation marking means it meets the disconnect requirements for lockout/tagout procedures.

Where can I buy ENW24175?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
ENW24175