Skip to main content
Schneider Electric ENW24180

Schneider Electric ENW24180 EasyPact NW Switch Disconnector,

MPN ENW24180
Active

Schneider Electric EasyPact NW switch disconnector, ENW24180, 3-pole, 4000 A AC-23A, fixed mount, IP40, IEC 60947-3.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24180 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 4000 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24180 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width422 mm
Height352 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24180 is a 3-pole switch disconnector in the EasyPact NW range, rated for 4000 A in AC-23A duty at 690 V AC. That AC-23A utilisation category means it handles switching of motor loads and other highly inductive circuits — not just resistive break — so it's sized for heavy distribution or large motor feeder isolation where frequent on-load switching is expected. Rated insulation voltage sits at 1000 V AC, with an impulse withstand of 12 kV per IEC 60947-3, and the short-time withstand current is 55 kA for 1 s or 30 kA for 3 s. The short-circuit making capacity hits 121 kA AC — that's the peak current it can close into a fault without welding contacts. For a 4000 A frame, those numbers give real selectivity headroom downstream. The IP40 enclosure keeps tools and fingers out but isn't sealed against water; mount it inside a panel or switchgear cubicle.

Deployment and integration

Fixed-mount design on a base plate, with rear connections spaced at 115 mm pitch without a spreader. That pitch is standard for busbar or cable tap-offs in LV switchgear. The 422 mm width and 352 mm height fit typical cubicle compartments; depth of 297 mm leaves room for rear cabling without forcing a deep enclosure. Continuous rated duty — no derating needed for sustained load. The contact position indicator gives a visible break confirmation, which is required for isolation applications per IEC 60947-3. Suitability for isolation is explicitly marked as 'Yes' on the standard.

Electrical durability is specified at 5000 cycles at 440 V and 2500 cycles at 690 V in AC-23A without maintenance. Mechanical durability reaches 20000 cycles with maintenance, 10000 without. Those are the numbers to plug into your maintenance schedule — after that, contact wear inspection is due.

MPN
ENW24180