Specifications

Identification

ENW24180 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24180 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 4000 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24180 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)55 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 30 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)121 kA AC at 50/60 Hz

Performance

ENW24180 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24180 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24180 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24180 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24180 is a 3-pole switch disconnector in the EasyPact NW range, rated for 4000 A in AC-23A duty at 690 V AC. That AC-23A utilisation category means it handles switching of motor loads and other highly inductive circuits — not just resistive break — so it's sized for heavy distribution or large motor feeder isolation where frequent on-load switching is expected. Rated insulation voltage sits at 1000 V AC, with an impulse withstand of 12 kV per IEC 60947-3, and the short-time withstand current is 55 kA for 1 s or 30 kA for 3 s. The short-circuit making capacity hits 121 kA AC — that's the peak current it can close into a fault without welding contacts. For a 4000 A frame, those numbers give real selectivity headroom downstream. The IP40 enclosure keeps tools and fingers out but isn't sealed against water; mount it inside a panel or switchgear cubicle.

Deployment and integration

Fixed-mount design on a base plate, with rear connections spaced at 115 mm pitch without a spreader. That pitch is standard for busbar or cable tap-offs in LV switchgear. The 422 mm width and 352 mm height fit typical cubicle compartments; depth of 297 mm leaves room for rear cabling without forcing a deep enclosure. Continuous rated duty — no derating needed for sustained load. The contact position indicator gives a visible break confirmation, which is required for isolation applications per IEC 60947-3. Suitability for isolation is explicitly marked as 'Yes' on the standard.

Electrical durability is specified at 5000 cycles at 440 V and 2500 cycles at 690 V in AC-23A without maintenance. Mechanical durability reaches 20000 cycles with maintenance, 10000 without. Those are the numbers to plug into your maintenance schedule — after that, contact wear inspection is due.