Skip to main content
Schneider Electric ENW24187

Schneider Electric ENW24187 EasyPact NW Switch Disconnector,

MPN ENW24187
Active

Schneider Electric EasyPact NW switch disconnector, ENW24187, 3200 A AC-23A, 4 poles, drawout mounting, 690 V AC, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24187 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 3200 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24187 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24187 is a 4-pole switch disconnector from the EasyPact NW range, rated for 3200 A in AC-23A duty at 690 V AC. It's certified as a disconnector (isolator) per IEC 60947-3, so it provides visible-break isolation for a feeder or distribution panel.

Rated operational current of 3200 A in AC-23A at 690 V. This governs motor feeder applications. Short-time withstand (Icw) is 50 kA for 1 second or 25 kA for 3 seconds — that tells you the switch can ride through a fault until an upstream breaker clears it, without welding shut or exploding. The making capacity of 105 kA peak confirms it can close onto a bolted fault and survive. Rated insulation voltage (Ui) of 1000 V AC and impulse withstand (Uimp) of 12 kV give headroom for 690 V systems and cover surge coordination in industrial networks. IP40 protection means it's splash-proof from tools and fingers but not water jets — install inside a panel or enclosure.

Mechanical and electrical endurance

Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V under AC-23A without maintenance — that's the contact wear life. Mechanical durability is 20000 cycles with maintenance, 10000 without. For a drawout switch at this current level, those numbers are typical for a main feeder disconnector that sees infrequent operation.

MPN
ENW24187