Schneider Electric ENW24187 — Air Circuit Breakers

Schneider Electric ENW24187 EasyPact NW Switch Disconnector,

MPNENW24187
Active

Schneider Electric EasyPact NW switch disconnector, ENW24187, 3200 A AC-23A, 4 poles, drawout mounting, 690 V AC, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24187 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24187 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 3200 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24187 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz

Performance

ENW24187 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24187 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24187 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24187 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24187 is a 4-pole switch disconnector from the EasyPact NW range, rated for 3200 A in AC-23A duty at 690 V AC. It's certified as a disconnector (isolator) per IEC 60947-3, so it provides visible-break isolation for a feeder or distribution panel.

Rated operational current of 3200 A in AC-23A at 690 V. This governs motor feeder applications. Short-time withstand (Icw) is 50 kA for 1 second or 25 kA for 3 seconds — that tells you the switch can ride through a fault until an upstream breaker clears it, without welding shut or exploding. The making capacity of 105 kA peak confirms it can close onto a bolted fault and survive. Rated insulation voltage (Ui) of 1000 V AC and impulse withstand (Uimp) of 12 kV give headroom for 690 V systems and cover surge coordination in industrial networks. IP40 protection means it's splash-proof from tools and fingers but not water jets — install inside a panel or enclosure.

Mechanical and electrical endurance

Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V under AC-23A without maintenance — that's the contact wear life. Mechanical durability is 20000 cycles with maintenance, 10000 without. For a drawout switch at this current level, those numbers are typical for a main feeder disconnector that sees infrequent operation.

Frequently asked questions

What is ENW24187's listed depth?

The ENW24187 has a depth of 395 mm, with width 556 mm and height 439 mm.

What compliance documentation does Schneider provide for ENW24187?

The ENW24187 is certified to IEC 60947-3 for switch-disconnector function and isolation suitability. Pollution degree 4 per IEC 60664-1. Specific RoHS/REACH/UL declarations should be requested with the RFQ.

MPN