Skip to main content
Schneider Electric ENW24239

ENW24239 EasyPact NW Circuit Breaker, 1250 A, 50 kA Icu

MPN ENW24239
Active

Schneider Electric EasyPact NW, ENW24239, 4-pole fixed circuit breaker, 1250 A rated at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24239 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24239 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The ENW24239 is a Schneider Electric EasyPact NW 4-pole fixed circuit breaker rated 1250 A at 40 °C. That 1250 A continuous rating governs the main feeder or bus tie it can protect — size the upstream transformer or generator accordingly. The 50 kA Icu at 220…440 V AC tells you it can safely interrupt a fault up to that level without rupturing; below 440 V the full 50 kA holds, at 690 V it derates to 42 kA Icu. The Ics service breaking capacity matches the Icu at both voltage levels, meaning after clearing a fault at rated breaking capacity the breaker remains functional — no immediate replacement needed for a downstream short. The IP40 enclosure keeps out tools and wires over 1 mm but is not sealed against moisture — mount indoors or in a cabinet.

Deployment context

This is a fixed-mount breaker on a base plate, not a draw-out unit — plan for bolted connections and rear access. The 537 mm width, 352 mm height, and 297 mm depth define the panel cutout and enclosure size. Connection pitch is 115 mm without spreader, which matters when laying out bus bars or cable lugs. The neutral is on the right. Category B utilisation means it's designed for distribution duty with no intentional delay on short-circuit — coordination studies should treat it as instantaneous above the magnetic pickup.

Designed and tested to IEC 60947-2 for low-voltage switchgear and controlgear. Electrical durability at 440 V is 6,000 cycles without maintenance, dropping to 4,000 cycles at 690 V. Maximum breaking time is 25 ms; maximum closing response time is 70 ms.

MPN
ENW24239