Schneider Electric ENW24239 — Air Circuit Breakers

ENW24239 EasyPact NW Circuit Breaker, 1250 A, 50 kA Icu

MPNENW24239
Active

Schneider Electric EasyPact NW, ENW24239, 4-pole fixed circuit breaker, 1250 A rated at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24239 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24239 — Electrical ratings
ParameterValue
Rated current (In)1250 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24239 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24239 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24239 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24239 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24239 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The ENW24239 is a Schneider Electric EasyPact NW 4-pole fixed circuit breaker rated 1250 A at 40 °C. That 1250 A continuous rating governs the main feeder or bus tie it can protect — size the upstream transformer or generator accordingly. The 50 kA Icu at 220…440 V AC tells you it can safely interrupt a fault up to that level without rupturing; below 440 V the full 50 kA holds, at 690 V it derates to 42 kA Icu. The Ics service breaking capacity matches the Icu at both voltage levels, meaning after clearing a fault at rated breaking capacity the breaker remains functional — no immediate replacement needed for a downstream short. The IP40 enclosure keeps out tools and wires over 1 mm but is not sealed against moisture — mount indoors or in a cabinet.

Deployment context

This is a fixed-mount breaker on a base plate, not a draw-out unit — plan for bolted connections and rear access. The 537 mm width, 352 mm height, and 297 mm depth define the panel cutout and enclosure size. Connection pitch is 115 mm without spreader, which matters when laying out bus bars or cable lugs. The neutral is on the right. Category B utilisation means it's designed for distribution duty with no intentional delay on short-circuit — coordination studies should treat it as instantaneous above the magnetic pickup.

Designed and tested to IEC 60947-2 for low-voltage switchgear and controlgear. Electrical durability at 440 V is 6,000 cycles without maintenance, dropping to 4,000 cycles at 690 V. Maximum breaking time is 25 ms; maximum closing response time is 70 ms.

Frequently asked questions

What is the breaking capacity of ENW24239?

50 kA Icu at 220…440 V AC and 42 kA Icu at 690 V AC, both per IEC 60947-2. The Ics service breaking capacity matches those values.

What is the rated current of ENW24239?

1250 A at 40 °C ambient. The CT rating matches the breaker rating at 1250 A.

MPN
ENW24239