Skip to main content
Schneider Electric EVS40H3NW6A

Schneider EVS40H3NW6A EasyPact EVS Circuit Breaker, 4000 A,

MPN EVS40H3NW6A
Active

Schneider Electric EasyPact EVS series, EVS40H3NW6A, 3-pole drawout circuit breaker, 4000 A rated current, 65 kA Icu at 440 V AC, electronically controlled with EVS Trip System6A.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS40H3NW6A key specifications
ParameterValue
Control typeElectrically operated
Display typeDigital display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

EVS40H3NW6A additional specifications
ParameterValue
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Integrator note — EVS40H3NW6A

The Schneider Electric EVS40H3NW6A is a 3-pole drawout circuit breaker from the EasyPact EVS range, rated 4000 A at 40 °C and carrying a 65 kA Icu breaking capacity at 220…440 V AC 50/60 Hz per IEC 60947-2 (50 kA at 690 V AC). This is a Category B breaker — utilization class B per IEC 60947-2 — meaning it is designed for selectivity in distribution, with a deliberate short-time delay before tripping on a fault. The EVS Trip System6A electronic trip unit provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection. The drawout mounting (rail or base plate) allows the breaker to be racked out for maintenance without disturbing the rear-connected power cables. IP40 front-face protection suits indoor switchgear; pollution degree 4 per IEC 60664-1 means it tolerates conductive dust environments typical in heavy industrial distribution.

The 25 ms maximum breaking time means the arc is quenched within two cycles at 50 Hz, limiting let-through energy for downstream equipment. Thermal memory holds a 20-minute pre- and post-trip heat profile, so a reclose after a near-trip event will not falsely trip on a cold start — important for motor or transformer feeders where inrush repeats.

Panel integration & compliance

Dimensions: 441 mm wide × 439 mm high × 395 mm deep. Rear connection with a 115 mm pole pitch (without spreader). Vertical or horizontal connection positions give flexibility in busbar layout. The digital display on the trip unit shows fault cause (overload, short-circuit, earth fault, internal fault) for rapid troubleshooting. Mechanical durability is 20,000 cycles with maintenance, 10,000 without; electrical durability is 5,000 cycles at rated voltage without maintenance — figures that govern the breaker's service life in high-cycle applications like capacitor bank switching or motor starting.

MPN
EVS40H3NW6A