Skip to main content
Schneider Electric EZC250H3125

Schneider Electric EZC250H3125 EasyPact EZC250H Circuit Brea

MPN EZC250H3125
Active

Schneider Electric EasyPact EZC250H series, EZC250H3125, 3-pole circuit breaker, 125 A rated current, thermal-magnetic TM-D trip unit, 36 kA breaking capacity at 415 V AC, IP20, backplate mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC250H3125 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C

All specifications

EZC250H3125 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Depth60 mm
Width105 mm
Height165 mm
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The EZC250H3125 is a 3-pole thermal-magnetic circuit breaker from Schneider Electric's EasyPact EZC250H line, rated 125 A at 40 °C and 125 A at 50 °C — the lower ambient derates the trip unit, so a 125 A continuous load at 50 °C needs the next frame up. The TM-D trip unit provides short-circuit and overload protection with a fixed thermal and magnetic curve, no adjustment. Breaking capacity varies by voltage: 36 kA Icu at 400–415 V AC is the figure most panel builders will check for 400 V distribution — it tells you the breaker can safely clear a fault up to 36 kA without welding contacts or rupturing the case. For DC circuits, it delivers 30 kA Icu at 125 V DC (1-pole) and 30 kA Icu at 250 V DC (2-pole). IK07 means it survives a 2 J impact, typical for switchgear handling.

This breaker mounts to a backplate with fixed mounting — not DIN rail, so plan for screw-down lugs or a dedicated mounting bracket. Both line and load connections are front-facing, so busbar or cable routing stays on one plane — useful for stacked breaker layouts. Connection pitch is 35 mm, which matches standard busbar spacing for 3-pole breakers. The toggle control gives positive contact indication — you can see the contact position through the front window. Mechanical durability is 10,000 cycles — fine for distribution, not for frequent switching duty.

The breaker is certified to GB/T 14048.2, EN/IEC 60947-2, and JIS C8201-2-2. Network frequency is 50/60 Hz. The device is designed for distribution applications.

MPN
EZC250H3125