Skip to main content
Schneider Electric GV4L02N

Schneider Electric GV4L02N TeSys Deca Motor Circuit Breaker,

MPN GV4L02N
Active

Schneider Electric TeSys Deca GV4, motor circuit breaker, GV4L02N, 3P, 2 A rated current, 100 kA breaking capacity at 240 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4L02N key specifications
ParameterValue
Control typeRotary handle
Trip unit typeMagnetic Electronic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC conforming to IEC 60947-2
IP ratingIP40
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C

All specifications

GV4L02N additional specifications
ParameterValue
Pollution degree3
ColorGrey (RAL 7016)
Depth165 mm
Width81 mm
Height155 mm
Electrical life cycles40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-25...70 °C

Product details

It's designed for motor protection in industrial control panels, combining a magnetic and electronic trip unit to handle both overload and short-circuit faults.

Rated current is 2 A, but the magnetic tripping range spans 12 to 28 A — this covers motor inrush without nuisance trips on smaller motors. The motor power table shows it's sized for motors from 0.25 kW up to 1.5 kW depending on line voltage (400 V to 690 V AC). Utilisation category AC-3 means it's rated for switching squirrel-cage motors during running, not just isolating them. The 40000-cycle electrical durability at AC-3, 440 V gives a realistic service life for a panel that sees a few cycles per hour.

The EverLink BTR screw connectors accept cables from 1.5 mm² up to 95 mm², with separate torque specs for smaller and larger conductors (5 N·m for 1.5–10 mm², 9 N·m for 16–95 mm²). IP40 protection means it's fine for dry indoor panels but not for washdown environments.

Certified to EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers). Suitable for isolation per IEC 60947-1. Fire resistance tested to 960 °C per IEC 60695-2-11.

MPN