Skip to main content
Schneider Electric GV4L02N — Motor Protection Circuit Breakers (MPCB)

Schneider Electric GV4L02N TeSys Deca Motor Circuit Breaker,

MPNGV4L02N
Active

Schneider Electric TeSys Deca GV4, motor circuit breaker, GV4L02N, 3P, 2 A rated current, 100 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GV4L02N — Mechanical
ParameterValue
Height155 mm
Width81 mm
Depth165 mm

Product details

It's designed for motor protection in industrial control panels, combining a magnetic and electronic trip unit to handle both overload and short-circuit faults.

Rated current is 2 A, but the magnetic tripping range spans 12 to 28 A — this covers motor inrush without nuisance trips on smaller motors. The motor power table shows it's sized for motors from 0.25 kW up to 1.5 kW depending on line voltage (400 V to 690 V AC). Utilisation category AC-3 means it's rated for switching squirrel-cage motors during running, not just isolating them. The 40000-cycle electrical durability at AC-3, 440 V gives a realistic service life for a panel that sees a few cycles per hour.

The EverLink BTR screw connectors accept cables from 1.5 mm² up to 95 mm², with separate torque specs for smaller and larger conductors (5 N·m for 1.5–10 mm², 9 N·m for 16–95 mm²). IP40 protection means it's fine for dry indoor panels but not for washdown environments.

Certified to EN/IEC 60947-4-1 (motor starters) and EN/IEC 60947-2 (circuit breakers). Suitable for isolation per IEC 60947-1. Fire resistance tested to 960 °C per IEC 60695-2-11.

Frequently asked questions

What is the GV4L02N's depth?

The GV4L02N has a depth of 165 mm.

What range does the GV4L02N belong to?

It belongs to the Schneider Electric TeSys Deca range.

What compliance documentation is available for the GV4L02N?

The GV4L02N is certified to EN/IEC 60947-4-1 and EN/IEC 60947-2 standards. It is suitable for isolation per IEC 60947-1 and has fire resistance tested to 960 °C per IEC 60695-2-11.

MPN
GV4L02N