Skip to main content
Schneider Electric GV4L115B6

Schneider Electric GV4L115B6 TeSys Deca Motor Circuit Breake

MPN GV4L115B6
Active

Schneider Electric TeSys Deca GV4L115B6, motor circuit breaker, 115 A rated current, 37–110 kW motor power, 50 kA breaking capacity at 240 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4L115B6 key specifications
ParameterValue
Control typeRotary handle
Trip unit typeMagnetic Electronic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch27 mm without spreaders 35 mm with spreaders
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C

All specifications

GV4L115B6 additional specifications
ParameterValue
Pollution degree3
ColorGrey (RAL 7016)
Depth165 mm
Width81 mm
Height155 mm
Electrical life cycles10000 cycles for AC-3 at 440 V In/2 5000 cycles for AC-3 at 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-25...70 °C

Product details

What the 115 A rating means for fit

The GV4L115B6 is a 3-pole motor circuit breaker rated at 115 A continuous current, sized for motor loads between 37 kW and 110 kW depending on supply voltage. The 115 A frame is the selection anchor — it determines the upstream contactor and cable sizing, not just the motor full-load amps. Breaking capacity is 50 kA Icu at 240 V AC, 25 kA at 415 V, 20 kA at 440 V, and 10 kA at 500 V.

Motor protection and trip characteristics

Uses magnetic-electronic trip technology with a magnetic tripping range of 690...1610 A. That's the instantaneous short-circuit pickup — adjustable within that band to coordinate with downstream contactors and avoid nuisance trips on motor inrush. Rated for continuous duty per IEC 60947-4-1, so it handles sustained motor loads without derating.

Fire resistance rated at 960 °C per IEC 60695-2-11.

Panel and mounting notes

Dimensions: 155 mm high, 81 mm wide, 165 mm deep. Connection pitch is 27 mm without spreaders, 35 mm with spreaders. Terminals accept lugs or ring terminals — tightening torque 9 N·m for 16...95 mm² cable, 5 N·m for 1.5...10 mm². IP40 enclosure protection, IK07 impact resistance. Operating altitude up to 5000 m.