Skip to main content
Schneider Electric GV4LE07N6

Schneider Electric GV4LE07N6 TeSys GV4 Motor Circuit Breaker

MPN GV4LE07N6
Obsolete

Schneider Electric TeSys GV4 series, motor circuit breaker, GV4LE07N6, 3P, 7 A In, 100 kA Icu at 240 V AC, magnetic-electronic trip.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4LE07N6 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic Electronic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch27 mm without spreaders 35 mm with spreaders
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

GV4LE07N6 additional specifications
ParameterValue
Storage temperature-50...85 °C
Pollution degree3
ColorGrey (RAL 7016)
Depth116 mm
Width81 mm
Height155 mm
Electrical life cycles40000 cycles for AC-3 at 440 V In/2 40000 cycles for AC-3 at 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-25...70 °C

Product details

It's a 3-pole unit with a rated current of 7 A and uses a combined magnetic and electronic trip unit technology. Its primary job is to protect motor feeders against short-circuits and overloads, and it's rated for continuous duty per IEC 60947-4-1. The magnetic trip is adjustable between 42 and 98 A, covering a range of motor sizes. The breaker is rated for isolation per IEC 60947-1, meaning it can be used as a disconnecting means in the motor branch circuit.

The headline breaking capacity is 100 kA Icu at 220-240 V AC, which drops to 50 kA at 380-415 V and 15 kA at 525 V. The motor power ratings span from 1.5 kW at 400 V up to 7.5 kW at 690 V, so it fits a range of small to medium induction motors. For a 400 V line, it covers 1.5 to 3 kW motors depending on the exact rating. Utilization category is AC-3 per IEC 60947-4-1, which is the standard for squirrel-cage motor starting — switching motors during running, not just isolating them. It's also Category A per IEC 60947-2 for general circuit protection. Electrical durability is rated at 40,000 cycles under AC-3 at 440 V, both at full load and at half load. Mechanical durability matches at 40,000 cycles. That's a solid service life for a motor starter duty cycle in most industrial applications. Power dissipation per pole is 6.1 W, so total heat load in the enclosure is about 18.3 W.

Dimensions are 155 mm high, 81 mm wide, and 116 mm deep. It's designed for panel mounting with lugs or ring terminals, accepting cables from 1.5 to 95 mm². Tightening torque is 9 N.m for the larger cable range and 5 N.m for the smaller. The connection pitch is 27 mm without spreaders, or 35 mm with them — useful to know when laying out busbars or cable ducts in the enclosure. IK07 impact resistance handles light mechanical knocks during installation.

The GV4LE07N6 complies with EN/IEC 60947-2 (circuit-breaker standard) and EN/IEC 60947-4-1 (contactor and motor-starter standard). It also meets IEC 60695-2-11 for glow-wire fire resistance at 960 °C, and IACS for climatic withstand.

MPN
GV4LE07N6