Skip to main content
Schneider Electric GV4LE80B

Schneider Electric GV4LE80B TeSys Deca Motor Circuit Breaker

MPN GV4LE80B
Active

Schneider Electric TeSys Deca GV4LE80B motor circuit breaker, 3-pole, 80 A rated current, magnetic electronic trip, 50 kA Icu breaking capacity at 240 V AC.

$341.18 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4LE80B key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic Electronic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C

All specifications

GV4LE80B additional specifications
ParameterValue
Pollution degree3
ColorGrey (RAL 7016)
Depth116 mm
Width81 mm
Height155 mm
Electrical life cycles14000 cycles for AC-3 at 440 V In/2 7000 cycles for AC-3 at 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-25...70 °C

Product details

It is rated at 80 A continuous current and carries motor power ratings of 37 kW at 400–415 V AC, 45 kW at 500 V AC, and 55 kW at 660–690 V AC, all at 50/60 Hz. The magnetic electronic trip unit provides adjustable magnetic tripping from 480 to 1120 A, covering inrush and locked-rotor conditions on the connected motor. Breaking capacity reaches 50 kA Icu at 240 V AC, 25 kA at 415 V, and 10 kA at 500 V, certified per IEC 60947-2. The utilisation category is AC-3 per IEC 60947-4-1, meaning it is rated for switching squirrel-cage motors during starting and running — the standard duty for motor circuit breakers in industrial lines. It also qualifies as Category A (no intentional short-time delay) per IEC 60947-2, appropriate for motor branch circuit protection where coordination with downstream contactors is handled separately.

Dimensions are 155 mm high, 81 mm wide, and 116 mm deep, fitting a standard DIN-rail enclosure footprint. The EverLink BTR screw terminals on top accept 1.5–70 mm² solid or 1.5–50 mm² flexible cable; bottom terminals accept 2.5–95 mm² solid or 2.5–70 mm² flexible. Tightening torque is 9 N·m for the larger (16–95 mm²) cable range and 5 N·m for the smaller (1.5–10 mm²) range. IP40 protection suits dry indoor panel environments; IK07 impact rating handles incidental tool contact during commissioning. Climatic withstand conforms to IACS for marine environments, so it can be specified for shipboard auxiliary panels.

If a second-source gate review is required, the TeSys Deca range includes other frame sizes at different current ratings, but the 80 A GV4LE80B is the direct fit for a 37 kW (400 V) motor branch.

The 80 A rated current (In) sets the continuous thermal capacity — this breaker will carry 80 A indefinitely without tripping, per IEC 60947-4-1 continuous duty. The magnetic electronic trip unit responds to short-circuit currents between 480 and 1120 A (6 to 14 times In), covering the typical locked-rotor current of a 37 kW motor while riding through normal starting inrush. For overload protection, the electronic trip provides adjustable time-current curves, though the specific thermal setting range is not listed here; the breaker is designed to coordinate with a downstream TeSys contactor for full motor starter functionality. Electrical durability is 14,000 cycles at AC-3 duty with half rated current (In/2) and 7,000 cycles at full rated current (In) at 440 V. Mechanical durability is 40,000 cycles. These numbers define the maintenance interval: at one start per hour, the electrical contacts last roughly 2–3 years before replacement is prudent. The maximum operating rate of 25 cycles per hour sets a hard limit for jogging or rapid cycling applications. Power dissipation per pole is 6.1 W at rated current, totaling 18.3 W for the three poles. This heat must be considered in enclosure sizing — a sealed panel with multiple breakers may require forced ventilation or derating. The fire resistance rating of 960 °C per IEC 60695-2-11 ensures the enclosure material will not propagate a flame under fault conditions.

MPN
GV4LE80B