Skip to main content
Schneider Electric GV4P50N6

Schneider GV4P50N6 Motor Circuit Breaker, 50 A, TeSys Deca

MPN GV4P50N6
Active

Schneider Electric TeSys Deca GV4P50N6 motor circuit breaker, 3-pole, 50 A rated line current, electronic thermal-magnetic trip, 100 kA breaking capacity at 240 V AC, IP40, gray RAL 7016.

$1,031.03 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4P50N6 key specifications
ParameterValue
Control typeRotary handle
Trip unit typeElectronic Thermal-magnetic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz IEC 60947-2
Utilization categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IP ratingIP40
Terminal pitch1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

GV4P50N6 additional specifications
ParameterValue
Storage temperature-58...185 °F (-50...85 °C)
Pollution degree3
ColorGray RAL 7016)
Depth6.5 in (165 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical life cycles20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-13...158 °F (-25...70 °C)

Product details

Breaking capacity that covers the fault-current map

The GV4P50N6: At 240 V AC the Icu is 100 kA per IEC 60947-2, dropping to 50 kA at 415 V and 25 kA at 500 V. Under UL 60947 the 480Y/277 V rating is 35 kA. These are not theoretical maximums — they are the tested interrupting ratings that let you coordinate downstream without cascading failure. The 50 A line current coupled with an 850 A magnetic trip threshold means the short-circuit release is set at 17× In, which sits above motor inrush but below the fault current the supply can deliver. That selectivity window is what keeps a single motor fault from taking out the whole panel.

AC-3 motor duty and thermal budget

Rated utilisation category AC-3 per IEC 60947-4-1 — this is the standard for squirrel-cage motors with starting currents up to 8× In. The GV4P50N6 covers 11 kW at 400 V and up to 45 kW at 690 V, which brackets the common IEC motor frame sizes from 132 to 225. Power dissipation is 4.6 W per pole. In a closed panel with multiple breakers ganged, that 13.8 W three-phase heat adds up — the IP40 enclosure assumes free air, so derate the grouping factor if you pack them tighter than the 27 mm pole pitch without spreaders.

Dimensions are 3.2 in wide × 6.1 in tall × 6.5 in deep (81 × 155 × 165 mm). The 27 mm pole pitch matches the standard TeSys Deca busbar grid; with spreaders it opens to 35 mm for larger cable lugs. Terminals accept lugs or ring terminals: the main circuit takes 16–95 mm² at 9 N·m, the control circuit 1.5–10 mm² at 5 N·m. That covers both the motor feeder and the control wiring in one terminal block.

Approvals and compliance for global panels

The fire-resistance glow-wire test passes at 960 °C per IEC 60695-2-11. Pollution degree 3 means it is rated for the conductive-dust environment inside a typical industrial enclosure.

MPN