Skip to main content
Schneider Electric GV4PE50B6

Schneider GV4PE50B6 TeSys Deca MPCB, 50 A, 50 kA Icu

MPN GV4PE50B6
Obsolete

Schneider Electric TeSys Deca GV4PE50B6 motor circuit breaker, 3-pole, 50 A line rated current, 50 kA Icu at 240 V AC, electronic thermal-magnetic trip, IP40, gray RAL 7016.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

GV4PE50B6 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic Thermal-magnetic
Main product or component typeMotor circuit breaker
Voltage690 V AC 50/60 Hz IEC 60947-2
Insulation voltage ui800 V AC 50/60 Hz IEC 60947-2
Breaking capacity50 kA Icu 220...240 V AC 50/60 Hz IEC 60947-2 25 kA Icu 380...415 V AC 50/60 Hz IEC 60947-2 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA 208Y/120 V AC 50/60 Hz UL 60947 35 kA 240 V AC 50/60 Hz UL 60947 18 kA 480Y/277 V AC 50/60 Hz UL 60947 14 kA 600Y/347 V AC 50/60 Hz UL 60947
Utilization categoryCategory A IEC 60947-2 AC-3 IEC 60947-4-1
IP ratingIP40
Terminal pitch1.06 in (27 mm) without spreaders 1.4 in (35 mm) with spreaders
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

GV4PE50B6 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-58...185 °F (-50...85 °C)
Pollution degree3
ColorGray RAL 7016)
Depth4.6 in (116 mm)
Width3.2 in (81 mm)
Height6.1 in (155 mm)
Electrical life cycles20000 cycles AC-3 440 V In/2 10000 cycles AC-3 440 V In
Mechanical life cycles40000 cycles
ApplicationMotor protection
Operating positionAny position
Operating temperature-13...158 °F (-25...70 °C)

Product details

50 A motor circuit breaker with 50 kA interrupting capacity

The GV4PE50B6: The trip unit uses an electronic thermal-magnetic hybrid, which means the thermal curve handles overload protection with a programmable-like response while the magnetic element catches short-circuit events at 850 A magnetic tripping current. The electronic side also enables phase failure sensitivity per IEC 60947-4-1 — a feature that drops the breaker when one phase is lost, preventing single-phasing damage on a motor load.

Motor power coverage and load matching

At 400–415 V AC, the GV4PE50B6 covers motor ratings from 11 kW up to 22 kW depending on the voltage tap. At 500 V it handles 15–30 kW, and at 660–690 V it spans 18.5–45 kW. That's a wide power band for a single frame size — the 50 A setting lets you dial in the exact motor FLA within the adjustable range of the TeSys Deca platform. Mechanical durability is 40,000 cycles. The maximum operating rate is 25 cycles per hour — relevant for frequent start-stop applications like conveyors or pump cycling.

Panel fit and environmental ratings

Dimensions are 6.1 x 3.2 x 4.6 inches (155 x 81 x 116 mm). The connection pitch is 27 mm without spreaders, expanding to 35 mm with spreaders — the spreaders give extra clearance for larger cable lugs in a crowded enclosure. Terminal capacity accepts 1.5–95 mm² wire. IK07 impact resistance covers accidental tool drops.

Certification and compliance coverage

That covers the three major regional approval frameworks — UL for North America, CSA for Canada, and IEC/EN for global and European markets. Fire resistance is tested to 960 °C per IEC 60695-2-11.

MPN
GV4PE50B6