Skip to main content
Schneider Electric LA4DFE

TeSys LA4DFE interface module, 48 V DC / 250 V AC

MPN LA4DFE
Obsolete

Schneider Electric TeSys D LA4DFE interface amplifier module, relay output, 48 V DC control / 250 V AC switching, top-mounted on contactor.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LA4DFE specifications
ParameterValue
Protection typeBuilt-in by diode
Main product or component typeInterface module
VoltageControl circuit 24...250 V AC
Insulation voltage ui250 V - control circuit IEC 60947-5-1
Current15 mA 68 °F (20 °C)
IP ratingIP2X
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max55 °C
Temp operating min-25 °C
Storage temperature-40...176 °F (-40...80 °C)
Height0.5 in (12 mm)
Electrical life cycles10 Mcycles 240 V
Operating temperature-13...131 °F (-25...55 °C)
Permissible ambient air temperature around the device-13...158 °F (-25...70 °C)

Product details

The Schneider Electric TeSys D LA4DFE is an interface amplifier module that sits between a low-level DC control signal and a contactor coil. It accepts a 48 V DC control supply and switches up to 250 V AC on the output side, letting a PLC or safety relay with a limited DC output drive a standard AC contactor coil. The module top-mounts directly onto a TeSys D contactor — no additional DIN-rail footprint needed. The built-in diode provides coil suppression, and an LED gives local status indication.

Control voltage limits span 33...60 V DC at 20 °C, so a nominal 48 V DC supply with typical ±10 % tolerance (43.2...52.8 V) sits comfortably inside the window. The module draws 15 mA from that supply. State 0 is guaranteed at ≤ 1.3 mA and < 4.8 V, which means most PLC digital outputs with a low-side leakage under 2 mA will reliably turn the module off. On the output side, the rated operational voltage covers 24...250 V AC. The insulation voltage is rated 250 V per IEC 60947-5-1, so the module is sized for standard 240 V control circuits.

Installation notes

Top-mounts onto the contactor — no DIN rail consumed. The IP2X finger protection (VDE 0106) is typical for enclosed panel gear; not rated for washdown. Heat dissipation is 0.6 W on the control circuit — negligible for panel thermal budgeting. Ambient operating range is -25...55 °C, storage -40...80 °C. The TH protective treatment per IEC 60068 covers tropicalized environments.

MPN
LA4DFE