Schneider Electric LC1F1154M7 TeSys F Contactor, 200 A AC-1,

MPN LC1F1154M7
Obsolete

Schneider Electric TeSys F, LC1F1154M7, 4-pole contactor, 200 A AC-1, 220 V AC 40-400 Hz coil, plate mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LC1F1154M7 key specifications
ParameterValue
Control circuit typeAC at 40...400 Hz
Main product or component typeContactor
Voltage<= 460 V DC
Coil voltage220 V AC 40...400 Hz
Insulation voltage ui1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C
Current200 A (at <40 °C) at <= 440 V AC-1
Breaking capacity920 A conforming to IEC 60947-4-1
Utilization categoryAC-1
Temp storage max80 °C
Temp storage min-60 °C
Temp operating max60 °C
Temp operating min-40 °C

All specifications

LC1F1154M7 additional specifications
ParameterValue
Storage temperature-60...80 °C
Depth171 mm
Width200.5 mm
Height162 mm
Mechanical life cycles10 Mcycles
ApplicationResistive load
Operating time35 ms closing at Uc) 130 ms opening at Uc)
Operating temperature-40...60 °C
Permissible ambient air temperature around the device60...70 °C at Uc

Product details

The 4 NO configuration gives you four independent normally-open poles, each rated for the full 200 A in AC-1. The coil pulls 770 VA inrush and holds at 8.1 VA, so your control transformer needs to handle that surge. Mechanical durability is 10 million cycles, and the contactor is rated for 2400 operations per hour at 55 °C — fine for frequent switching in a process heater or oven. The control circuit is AC only (40-400 Hz), with a drop-out range of 20-55% of Uc and an operating range of 85-110% of Uc at 55 °C. That means the coil will drop out reliably between 44 and 121 V AC on a 220 V nominal supply — good for brownout ride-through on a resistive load bank. The rated impulse withstand voltage is 8 kV, and the insulation voltage is 1000 V per IEC 60947-4-1, so it's comfortable in 480 V panels with proper overvoltage category III coordination.

Plate-mounted only — no DIN-rail adapter. The dimensions are 162 mm high, 200.5 mm wide, and 171 mm deep, so it needs a solid backplate with clearance for the power circuit bolted connections. Power terminals accept bar (up to 20 x 3 mm busbar), ring lugs up to 95 mm², or connectors for 95 mm² cable. Control wiring uses screw clamp terminals accepting 1 to 4 mm² solid or flexible (with or without ferrule). Tighten power connections to 10 N·m and control connections to 1.2 N·m. The front face with shrouds is IP2X per IEC 60529 and VDE 0106 — finger-safe once shrouded, but not sealed against dust or moisture.