Skip to main content
Schneider Electric LV846171

Schneider Electric LV846171 MasterPact MTZ2 1000A 3P Drawout

MPN LV846171
Active

Schneider Electric MasterPact MTZ2, LV846171, 3-pole drawout circuit breaker, 1000 A rated current, H2V 100 kA at 415 V AC performance class.

$3,755.97 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846171 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846171 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width441 mm
Height439 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

What this breaker carries — and what that means for the line

The LV846171 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 1000 A at 40 °C. The H2V performance class means it interrupts faults up to 100 kA at 415 V AC, which puts it in the high-breaking-capacity tier for industrial distribution where fault currents are stiff and coordination with downstream gear matters. Drawout mounting means the breaker chassis stays bolted to the switchgear, and the moving portion slides out for inspection or swap without pulling cables. That cuts downtime on a line-down event — you rack it out, slide in a spare, and get back to making clinker. The 441 mm width and 439 mm height fit standard MasterPact MTZ2 cubicle cutouts; depth is 403 mm, which you need to account for in the enclosure depth before you spec the gland plate.

Breaking capacity — the number that governs coordination

The Ics (service breaking capacity) matches at 100 kA — meaning after a fault at full rating the breaker can be reclosed and carry rated current without immediate replacement. That is Category B selectivity, so it coordinates with downstream breakers: a fault on a branch trips the branch breaker, not this main, keeping the rest of the plant live. For a cement plant where losing the main kills the kiln feed, that selectivity keeps the raw mill running while a downstream fault clears. Short-time withstand (Icw) is 100 kA for 0.5 s and 1 s, and 75 kA for 3 s. That tells you the breaker holds closed under fault current long enough for downstream devices to clear — essential for selective coordination. The making capacity (Icm) is 220 kA at 440 V AC, which covers the worst-case asymmetrical peak when closing into a bolted fault.

What the standards tell you about where it goes

Compliant with EN/IEC 60947-1 (general rules), EN/IEC 60947-2 (circuit-breakers), and Annex H for EMC. Also meets IEC 61557-12 for power metering if equipped with the optional metering module. Altitude derating starts above 2000 m — fine for most cement plants unless you are at a highland site.

MPN