Skip to main content
Schneider Electric LV846176

LV846176 MasterPact MTZ2 3P 3200 A Circuit Breaker, 100 kA

MPN LV846176
Active

Schneider Electric MasterPacT MTZ2, LV846176, 3P drawout circuit breaker, 3200 A rated current, 100 kA breaking capacity at 440 V AC.

$11,389.68 – $16,211.77 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846176 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846176 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width441 mm
Height439 mm
Electrical life cycles5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

What this breaker is

The LV846176 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, 3-pole, rated 3200 A at 40 °C. It's the H2V performance variant, meaning 100 kA Icu/Ics at 440 V AC — that's the short-circuit rating that governs fault clearance in a main or tie breaker position. Category B selectivity (per IEC 60947-2) means it holds coordination downstream without nuisance tripping on transient faults, which is the difference between a momentary sag and a full plant blackout in a selective-coordination study.

Icu of 100 kA at 440 V AC is the ultimate breaking capacity — the breaker clears one fault at that level and must be replaced afterward. Ics is the same 100 kA at 440 V, meaning service breaking capacity equals ultimate: after clearing a fault at full rating, the breaker stays operational. That's unusual at this current level; most designs trade Ics at 50-75% of Icu. Icw (short-time withstand) is 100 kA for 1 second, which supports delayed-tripping coordination with downstream feeders. Icm (making capacity) is 220 kA at 440 V — the peak let-through the breaker must close into without welding contacts.

Integration notes

Drawout mounting on rails or base plate, with front and rear connection options top and bottom. Connection pitch is 115 mm. The breaker itself is 441 mm wide, 439 mm high, 403 mm deep — verify the cell dimensions in your switchgear against the drawout cradle envelope. IP30 enclosure protection; pollution degree 3 per IEC 60947-1, which is the standard industrial environment with conductive pollution. No control unit included (ordered separately), so factor in the Micrologic trip unit for the BOM.

MPN