Skip to main content
Schneider Electric LV846210

Schneider LV846210 MasterPact MTZ2 08 H2V, 800 A, 100 kA

MPN LV846210
Active

Schneider Electric MasterPacT MasterPact MTZ2 08 H2V, drawout circuit breaker, 4P, 800 A at 40 °C, 100 kA Ics at 440 V AC, H2V performance level.

$4,481.73 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846210 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846210 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width556 mm
Height439 mm
Electrical life cycles10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 10000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 08 H2V — 800 A Drawout Breaker, 100 kA Ics

The Schneider Electric LV846210 is a MasterPact MTZ2 08 H2V drawout circuit breaker, part of the MasterPacT range. The H2V performance level delivers 100 kA Ics (service breaking capacity) at 440 V AC 50/60 Hz, with a corresponding Icm (making capacity) of 220 kA at the same voltage. This SCCR headroom allows the breaker to clear high-fault currents without upstream coordination issues in Category B selective systems. Rated insulation voltage (Ui) is 1000 V AC, impulse withstand (Uimp) is 12 kV, and short-time withstand (Icw) is 100 kA for 0.5 s or 1 s, and 75 kA for 3 s. Maximum breaking time is 25 ms, with a closing response time of 70 ms.

Drawout Mounting and Integration

Drawout mounting allows the breaker to be racked in and out of the cassette without disturbing power or control wiring — essential for maintenance and safe isolation in metal-enclosed switchgear. Mounting support options include rails or a base plate. Connection pitch is 115 mm, and both upside and downside connections are available in front or rear configurations. Dimensions are 556 mm wide × 439 mm high × 403 mm deep. The neutral pole is on the right. Control is via push-button; the unit ships without a separate control unit.

Environmental and Standards Compliance

Operates in ambient temperatures from -25 to 70 °C, stores from -40 to 85 °C. IP30 protection per EN 60529. Power dissipation is 100 W at rated current. Meets EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-2 Annex H, and IEC 61557-12. Electrical durability is 10,000 cycles at 440 V AC under AC-23A, 6,000 cycles under AC-3. Mechanical durability is 15,000 cycles with periodic preventive maintenance.

MPN