Skip to main content
Schneider Electric LV846213

Schneider Electric LV846213 MasterPact MTZ2 1600A 4P Circuit

MPN LV846213
Active

Schneider Electric MasterPacT series, MasterPact MTZ2 drawout circuit breaker, LV846213, 4P, 1600 A at 40 °C, H2V 100 kA 415 V AC performance type.

$6,954.66 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846213 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846213 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width556 mm
Height439 mm
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 1600 A — selectivity and breaking capacity for main distribution

The Schneider Electric LV846213 is a MasterPact MTZ2 drawout circuit breaker rated 1600 A at 40 °C, 4 poles, with a H2V performance type delivering 100 kA breaking capacity at 415 V AC. This places it in the Category B selectivity class per EN/IEC 60947-2, meaning it's designed for main incoming or large feeder duty where full discrimination with downstream breakers is required — a line-down event on a fault clears the branch, not the main. The making capacity (Icm) at 440 V AC is 220 kA, which is the peak let-through the breaker must close onto and hold under fault.

Drawout mounting and connection flexibility

Drawout mounting means the breaker chassis stays wired to the bus while the moving portion can be racked out for maintenance or swap — no need to disconnect power cables. Both upside and downside connections accept front or rear termination, which simplifies bus-bar routing in switchgear lineups. The connection pitch is 115 mm, and the mounting support accommodates rails or a base plate. Physical envelope: 556 mm wide × 439 mm high × 403 mm deep. Neutral is on the right.

Durability and environmental ratings

Electrical durability is 10,000 cycles at rated current at 440 V AC per EN/IEC 60947-2 (AC-23A), and 6,000 cycles per EN/IEC 60947-3 (AC-3). Mechanical durability is 15,000 cycles with periodic preventive maintenance. IP30 protection is typical for enclosed switchgear — the enclosure provides the higher IP rating. Operating altitude is 0 to 2000 m without derating, 2000 to 5000 m with derating.

MPN
LV846213