Skip to main content
Schneider Electric LV846216

LV846216 MasterPact MTZ2 3200 A Circuit Breaker, 100 kA

MPN LV846216
Active

Schneider Electric MasterPacT MasterPact MTZ2, LV846216, drawout circuit breaker, 4P, 3200 A at 40 °C, 100 kA Ics at 440 V AC, H2V performance.

$14,805.99 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV846216 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV846216 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth403 mm
Width556 mm
Height439 mm
Electrical life cycles5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-2 AC-23 A: 5000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440 V AC 50/60 Hz at In conforming to EN/IEC 60947-3
Mechanical life cycles15000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

The LV846216 is a Schneider Electric MasterPact MTZ2 drawout circuit breaker, part of the MasterPacT range. It's a 4-pole, 3200 A rated device (at 40 °C) built for power distribution protection in commercial and industrial switchboards. The H2V performance class delivers 100 kA Ics at 440 V AC — that's the service breaking capacity it can interrupt and then be reclosed without refurbishment, which matters for continuity in critical feeders.

Rated current is 3200 A at 40 °C ambient. If your switchgear room runs hotter, you'll need to derate — the operating range goes up to 70 °C, but the full 3200 A only holds at 40 °C. The Icw short-time withstand is 100 kA for 0.5 s and 1 s, and 75 kA for 3 s; that tells you the breaker can ride through a delayed trip coordination scheme without damage. Insulation voltage is 1000 V AC, impulse withstand 12 kV, so it's comfortable in 690 V systems with proper coordination, though the operational voltage here is rated at 440 V AC. Electrical durability is 5000 cycles at In under AC-23A (440 V), and 6000 cycles under AC-3. Mechanical durability is 15,000 cycles with periodic preventive maintenance. That's typical for a drawout breaker this size — it's not a daily-switching device; it's a protection and isolation device for a main or large feeder. The maximum breaking time is 25 ms, closing response 70 ms, so it clears faults fast enough for selective coordination.

This is a drawout breaker — the chassis stays wired in the switchboard, and the breaker element slides in and out for maintenance or replacement without disturbing the power connections. It mounts on rails or a base plate, with a 115 mm connection pitch. Both front and rear connections are available for upside and downside terminations, giving flexibility in busbar layout. Neutral is on the right. The IP30 rating means it's for indoor, clean environments — not washdown, not outdoor.

MPN
LV846216